Print E-mail
Mineral Insulated Trace Heating - Copper Sheathed Single Core Cable Data Sheet

BS Range of MI Heating Cables; These cables are available for onsite manufacture of heating elements. A comprehensive range of accessories is available to assist with assembly.

Served Cables; Are protected with High Density Polyethylene (HDPE) suitable for applications including burial in soil or concrete and for low temperature pipe tracing applications.

For more information please download our PDF, click here.

Copper Sheathed Single Core Heating Cables – Bare and HDPE Covered
Cable Reference Bare
Cable Reference HDPE Covered
Overall  Diameter mm
Conductor Resistance /m @20°C
Recommended Cold lead-in
Reference
OD mm

H122D2000


H122D2000HDPE
2.8
2.000

W122-C2.5-750V
5.3


H122D1250


H122D1250HDPE
2.8
1.250


W122-C2.5-750V
5.3


H122D800


H122D800HDPE
3.5
0.800


W122-C2.5-750V
5.3


H122D630

H122D630HDPE
4.0
0.630

W122-C2.5-750V
5.3

H122D450

H122D450HDPE
4.0
0.450

W122-C2.5-750V
5.3

H122D315

H122D315HDPE
4.3
0.315

W122-C2.5-750V
5.3

H122D220

H122D220HDPE
4.5
0.220

W122-C2.5-750V
5.3

H122D140

H122D140HDPE
4.9
0.140

W122-C2.5-750V
5.3

H122D100

H122D100HDPE
5.2
0.100

W122-C2.5-750V
5.3

H122C63

H122C63HDPE
3.2
0.063

W122-C2.5-750V
5.3

H122C40

H122C40HDPE
3.4
0.040

W122-C2.5-750V
5.3

H122C25

H122C25HDPE
3.7
0.025

W122-C6.0-750V
6.4

H122C17

H122C17HDPE
4.6
0.017

W122-C6.0-750V
6.4

H122C11

H122C11HDPE
4.9
0.011

W122-C6.0-750V
6.4

H122C7

H122C7HDPE
5.3
0.007

W122-C10.0-750V
7.3

H122C4

H122C4HDPE
5.9
0.004

W122-C16.0-750V
8.3
Conductor Resistance Tolerance +/-10% - 600v single conductor
 
Cupro- Nickel Cables are designed to provide increased corrosion protection especially in most conditions. The conductor is copper allowing long lengths to be used in applications such as long line pipe tracing.

Sheath temperatures can be as high as 400°C and resistances are from 0.004 ohms/m upto 1.6 ohms/m.

Can’t find what you’re looking for? Please contact us here.